As time passes, our collaboration with M/s. Fairford Electronics Ltd., UK has developing more bonds and a successful association with technical support from FEL. We at ‘Jayashree’ are introducing a ‘New Advance Soft Starter’ i.e. DFE Series which Ranges from DFE 2 to DFE 38.
The products specs at a glance..
DFE
Low Cost, Internally Bypassed Soft Starter
Main Features
- Internally Bypassed: Reduces cost because when the Soft
Starter has reached top of ramp the
Thyristors are bypassed, this reduces heat
and the size of the cabinet required.
- Substitution of Star/Delta Starters.
- Lower maintenance costs
- Less stress on auxiliary equipment when starting
- Reduced down time
- Low cost of ownership
- Simplified Installation.
Rapid build and install time.
- No need to change wiring configurations: All six wires of the start delta configuration
can be used to minimise installation and
design costs.
- Competitive with Star/Delta Starters.
- Longer life
- Less maintenance
- Lower cost of ownership
Operational Voltage (Ue) 230-460VAC rms 3 Phase (-15%+10%)
Rated Frequency 50-60 Hz +/- 2Hz
Index Rating Standard (DFE-02 - DFE-26) AC53a: 3-5: 99-10
Class 10A (DFE-02 to DFE-26) AC53a: 3-12: 99-10
Class 10A (DFE-30 – DFE-38) AC53b: 3-12: 1188
Class 10 (DFE-30 – DFE-38) AC53b: 3-23: 3577
Control Supply 24V DC Supplied externally to terminals X1-X2
Dfe-34 to Dfe-38 need a power supply capable of 3 amps for 1 second.
Power supply kit (12VA) available as part No. AMISC0005.
Soft Start/Stop Control 24V DC/110V AC galvanically isolated terminals A1-A2
Auxiliary Circuits (Relays) Run - 13/14, Ready - 23/24. 230VAC 3A, Ac11
Indication Multifunction LED on the front of the unit
Start Time 0.5 to 12 Seconds (DFE-02 to DFE-26)
0.5 to 25 Seconds (DFE-30 to DFE-38)
Stop Time 0 to 12 Seconds (DFE-02 to DFE-26)
0 to 25 Seconds (DFE-30 to DFE-38)
Power Terminals Input 1/L1, 3/L2 and 5/L3
Output 2/T1, 4/T2 and 6/T3
Up to 55kW IP20 rated wire clamping terminals
75kW to 280kW External Busbars
IP Rating Up to 55kW IP20
75kW to 280kW IP00
Ambient Temperature 0°C to 40°C
Above 40°C de-rate linearly by 2% of unit FLC per °C to a de-rate of 40% at 60°C
Transport and Storage -25°C to +60°C
Altitude 1000m. Above 1000m de-rate linearly by 1% of unit FLC per 100m to a maximum
altitude of 2000m.
Humidity Max. 85% non-condensing, not exceeding 50% at 40°C